For Sale by High To Low Voltage
Description
Condition: New Padmounted Switchgear
Phase: Three-phase
Primary Voltage: 15000V (15kV)
Configuration: Model 5 (VFI Switchgear)
Mounting Type Pad-Mounted
Phase Three-Phase Units
kV Class 15kV 12.5kA
Insulation Fluid Mineral Oil
Tank/Cabinet Material Mild Steel
Paint Standard Bell Green (Munsell 7GY 3.29/1.5)
Unit Type VFI
Number of Sides Double Sided
Qty of Ways 5 Ways
Model Selection Model 5W2
Selection A Features Source - Vacuum Switch (RVAC)
Selection A Handle One Three Phase Handle
Selection A Bushings 600 Amp Aluminum Deadbreak Bushings
Selection A Visible Break Not Required (Std)
Selection B Features Source - Vacuum Switch (RVAC)
Selection B Handle One Three Phase Handle
Selection B Bushings 600 Amp Aluminum Deadbreak Bushings
Selection B Visible Break Not Required (Std)
Selection C Features Tap - VFI
Selection C Handle One Three Phase Handle
Selection C Bushings 200 Amp Bushing Wells with Load-Break Inserts
Selection C Visible Break Not Required (Std)
Selection C CT Ratio 1000:1
Selection D Features Tap - VFI
Selection D Handle One Three Phase Handle
Selection D Bushings 200 Amp Bushing Wells with Load-Break Inserts
Selection D Visible Break Not Required (Std)
Selection D CT Ratio 1000:1
Selection E Features Tap - VFI
Selection E Handle One Three Phase Handle
Selection E Bushings 200 Amp Bushing Wells with Load-Break Inserts
Selection E Visible Break Not Required (Std)
Selection E CT Ratio 1000:1
Controls Tri-Phase Control
Phase TCC Card EF Curve (Phase)
Fault Indicator Provisions Standard Provisions (1.06" dia hole with removable SS backing plate)
Grounding Provisions 1/2"-13 UNC Stainless Steel Nuts (Standard)
Service Items Standard Drain Plug
Phase Diagram 1-Line Diagram
Motor Operator Options No Motor Ops
Motor Operator Voltage N/A
Junction Box None
Additional Accessories Record Drawing PDF
Test Report None