QTY 1 - Siemens New Surplus 3P 500KV 2000AMP Live Tank Breaker
See
General technical data | |
Technical data according to | IEC 62271-100 |
Brand | SIEMENS ENERGY |
Type | live Tank |
Model | 3AP2 FI-550 kV |
Mechanical Construction Data | |
Number of poles | 3 |
Number of circuit breaker operating mechanism | 3 |
Interrupter units per pole | 2 |
Seismic Level | 0.3 g according to IEC |
Wind Speed | 144 Km/h |
m.a.s.l. Operation | Up to 1,000 m |
Ambient Temperature Range | -50°C to 20°C. |
Insulation Capacity | |
Rated Voltage | 275 kV |
Design Voltage | 550 kV |
Frequency | 60 Hz |
Lightning impulse withstand voltage: | |
-Phase to ground | 1550 kV |
-Across the open breaker | 1550 kV |
Rated power frequency withstand voltage: | |
-Phase to ground | 620 kV |
-Across the open breaker | 800 kV |
Insulator | |
Material | Porcelain |
Color | Brown or Grey |
High-voltage terminals | NEMA 4 |
Creepage distance | 25 mm/kV L-L |
Creepage distance (total) | >10500 mm |
Operating mechanism unit | |
Degree of protection | IP 55 |
Material | Carbon steel painted in gray |
Arc quenching medium | |
Arc quenching medium | SF6+CF4 |
Rated pressure SF6 at 20°C | 8.0 bar |
Signal loss of SF6 at 20°C | 7.2 bar |
General lockout at 20°C | 7.0 bar |
No. of gas compartments/ density monitors | 3 |
SF6- leakage-rate/year (max) | <0.5 % |
Breaking Capacity | |
Rated normal current | 2000 Amp. |
Rated short-circuit breaking current | 40 kA |
Rated duration of short-circuit | 3 s |
Rated frequency | 60 Hz |
Rated operating sequence, required | O – 0.3s – CO – 3 min. – CO |
Rated short-circuit making current | 104 kA |
First-pole-to clear factor | 1.3 |
Phase opposition (short-circuit breaking | 10 kA |
Control unit Data | |
Control Voltage | 125 VDC |
Voltage of heating | 120 VAC |
Motor Voltage | 125 VDC 10/10/1 STANDARD WIRING |
Free auxiliary contacts, wired (NO/NC/W) | |
Circuit Breaker Scope of Supply | |
Operation and maintenance instruction manual | |
IEC Routine test protocols | |
SF6/CF4 gas needed for the first filling | |
Galvanized support structure for a height of 2.3 mts between the lower part o bushing and the lower part of the support structure. If a different height is needed extra costs will apply and a longer manufacturing time will possibly be required. | |
2 Grounding connectors for 4/0 AWG copper | |
Interpole cables AB & CB 7m BB 3 m | |