go to top
The World's Leading Online Marketplace for Used, New, and Surplus Industrial Machinery & Equipment ℠

2000 Amps, DVM custom Switchboard, 277 Volts, Type 1 encl, 3 sections, 36" x 36" section, 100kA max fault (2 available)

Manufacturer: Dvm
Amps: 2000
Stock # L008220

No Photos Available Yet

Ask the seller to send photos of this item.

Request Photos from Seller

For Sale by LEL Critical Equipment

Surplus Record Dealer Since 2015
Location: Spartanburg, SC
Contact Christopher Nye
Let the seller know you found their listing on Surplus Record!

Description

Description

Product Details: (2) Switchboard units available for purchase

  • Model: DVM Custom Switchboard
  • System Voltage: 480Y/277V 3Ph 4W 60Hz
  • System Ampacity: 2000A
  • Source Description: Single Main
  • Bussing: Silver Plated Copper
  • Neutral Bus: 100%
  • Max Available Fault Current (RMS): 100kA
  • Enclosure: Type 1
  • Accessibility: Front Only
  • Exterior Paint Color: ANSI 49
  • Lineup: Includes MasterPact MTZ Breaker(s)
  • Grounding: Copper Ground Bus and ground lug for each device
Dimensions:
  • 3 sections, each 36" wide and 36" deep
  • Overall dimensions: 108.00" W x 36.00" D x 91.5" H
  • Approximate weight: 3044.00 lbs / 1380.76 kgs
Incoming Requirements:
  • Suitable for use as a service entrance
  • Entry point: Left of lineup, through the bottom
  • Connection type: Cable
Mains:
  • 1 x 2000AF/2000AT, 100% rated, 3-pole, stored energy, fixed-mounted circuit breaker (UL Type MTZ 2)
  • Features:
    • Micrologic X 6.0: Long Time, Short Time, Instantaneous, Ground Fault protection
    • Energy Reduction Maintenance Setting (ERMS)
    • Auxiliary switches: 4A-4B
    • Overcurrent trip switch: 1A/1B Form C (SDE)
    • Programmable Contact Module (ESM)
    • Visual contact wear indication
    • Energy Reduction Maintenance Switch
Feeders:
  1. 1 x 1600AF/1600AT, 100% rated, 3-pole, stored energy, fixed-mounted circuit breaker (UL Type MTZ 2)
    • Micrologic X 6.0: Long Time, Short Time, Instantaneous, Ground Fault protection
    • Energy Reduction Maintenance Setting (ERMS)
    • Auxiliary switches: 4A-4B
    • Overcurrent trip switch: 1A/1B Form C (SDE)
    • Programmable Contact Module (ESM)
    • Visual contact wear indication
    • Energy Reduction Maintenance Switch
  2. 2 x 250AS/250AT, 480V, 80% rated, 100kA, 3-pole (UL Type JL)
    • Standard trip unit: Long Time, Short Time, Instantaneous
    • Overcurrent trip switch: 1A/1B Form C
  3. 2 x 400AS/400AT, 480V, 80% rated, 100kA, 3-pole (UL Type LL)
    • Standard trip unit: Long Time, Short Time, Instantaneous
  4. 2 x 600AS/600AT, 480V, 80% rated, 100kA, 3-pole (UL Type LL)
    • Standard trip unit: Long Time, Short Time, Instantaneous
  5. 2 x 800AS/800AT, 480V, 80% rated, 100kA, 3-pole (UL Type PL)
    • Standard trip unit: Long Time, Short Time, Instantaneous
Stock images used


Additional Information
ManufacturerDVM Custom Switchboard
Voltage480Y/277V 3Ph 4W 60Hz
BussingSilver-Plated Copper
Max Available Fault Current100 kA
AccessibilityFront Only
GroundingCopper Ground Bus
Circuit TypeUL Type MTZ 2
Amps2000A
System Amps2000 A
Neutral Bus100% Rated
Enclosure Type:Type 1
Exterior Paint ColorANSI 49
Overall Dimensions108.00" W x 36.00" D x 91.5" H

Get Your Price from LEL Critical Equipment!

Buyers Who Viewed This Listing Also Viewed:

2000 Amps, General Electric #THPC3620B, AV-Line switchboard, high pressure switch, THFP fused

Seller: Quantum Technology
Location: Shippensburg, PA
Mfr: General Electric
Model: THPC3620B
3x100A, 240V THFP Panelboard Units, 1x2000A, 600V, 3Pole, High Pressure Contact Switch, Shipping & Freight Logistics Freight Handling: Average handling lead time is 5 business days (varies by item size, carrier used, and shipping location). Freight Inspection (Crucial): For all freight deliveries, the buyer must ...more

2000 Amps, ITE/Siemens, FC-I Low-Voltage Switchboard, MLO, 4-wire, 240/120 Volt, 3PH

Seller: Brilliant Equipment Services
Location: Burlington, NC
Mfr: Ite/siemens
Model: FC-I FC-1
ITE Siemens FC-1 Switchboard 2000A 240/120V 3PH 4W MLO Main Lug 2000 Amp 3 Phase.

2000 Amps, Siemens #SB, Low Voltage Switchboard, 480Y/277 Volts

Seller: Atlas Electric Inc
Location: Spokane Valley, WA
Mfr: Siemens
Model: SB
Siemens SB 2000 Amp Low Voltage Switchboard 480Y/277 Volt, 5 Sections Total, First Section:, MCCB30062 2000 AMP, MCCB30060 800 AMP, MCCB30061 800 AMP, Second Section:, MCCB30063 200 AMP, MCCB30064 200 AMP, MCCB30065 600 AMP FRAME 450 AMP TRIP, MCCB30066 90 AMP, MCCB30067 40 AMP, MCCB30068 70 AMP, MCCB30069 70 AMP ...more

2000 Amps, Eaton #PRL-C, Main Bus Bar Switchgear Unit, 347/600 Volts, 4-Wire, 3-Ph., 2014

Seller: Lenmark Industries
Location: Langley, BC
Mfr: Eaton
Model: PRL-C
Year: 2014
SKU: 145866, Model: PRL-C, Year: 2014, Condition: Used, Electrical :, Amps: 2000 amps, Voltage: 347/600 volts, Phase: 3-phase, Dimensions: 53.00 (H) x 25.00 (W) x 91.00 (L) inches, Additional :, Main Bus Bar: 2000A, Voltage: 347/600V, Phase: 3, Wire: 4, Symmetrical Amp: 50kA.

2000 Amps, Square D #PAF362000DC1625, QED Power style switchboard, 500 V.DC

Seller: Equipment Recovery Corp
Location: Willoughby, OH
Mfr: Square D
Model: PAF362000DC1625
Square D _UNKNOWN_.